Fin Comparison Chart

Extruded Aluminum Fin

0.010” Thick

Aluminum

Platefin

0.020” Thick

Aluminum

Platefin

0.010” Thick

Copper

Platefin

0.010” Thick

Solder Coated

Copper

0.010” Thick

Applied

Aluminum

0.015” Thick

L-Footed

Aluminum

0.015” Thick

Embedded

Aluminum

Operational Criteria

Resistance to bending

Excellent

Fair

Excellent

Fair

Poor

Fair

Good

Good

Low pressure cleaning

Excellent

Good

Excellent

Good

Good

Good

Excellent

Excellent

High pressure cleaning

Excellent

Poor

Good

Poor

Poor

Poor

Good

Good

Fin / tube contact (effectiveness)

Excellent

Good

Good

Good

Excellent

Poor

Good

Excellent

Fin / tube contact (mechanical longevity)

Excellent

Good

Good

Good

Excellent

Fair

Good

Excellent

Fin / tube contact (protection from exposure)

Excellent

Good

Good

Good

Excellent

Poor

Good

Poor

Resistance to fouling (one row)

Good

Good

Good

Good

Good

Good

Good

Good

Resistance to fouling (multiple row)

Fair

Good

Good

Good

Fair

Fair

Fair

Fair

Mitigation of moisture carry-over

Fair

Excellent

Excellent

Excellent

Fair

Fair

Fair

Fair

Handling of thermal cycling

Good

Fair

Fair

Fair

Good

Fair

Good

Excellent

Handling of differential thermal expansion

Good

Fair

Fair

Fair

Good

Good

Good

Good

Handling of tube vibration

Fair

Good

Good

Good

Fair

Fair

Fair

Fair

Tube replacement

Replacement of individual finned tubes or re-tubing a finned tube exchanger is not considered and viable economical option.

Design Criteria

Fin spacing options (fins per inch)

Fair

Good

Good

Good

Excellent

Excellent

Good

Good

Fin thickness options

Poor

Good

Good

Good

Fair

Good

Good

Good

Fin height options

Fair

Poor

Poor

Poor

Fair

Good

Good

Good

Tube pitch / row pitch options

Excellent

Fair

Fair

Fair

Excellent

Excellent

Excellent

Excellent

Enhancement options

Poor

Excellent

Excellent

Excellent

Poor

Poor

Poor

Poor

Temperature limit *

450ºF

350ºF

375ºF

450ºF

450ºF

250ºF

350ºF

750ºF

Thermal effectiveness **

Fair

Good

Good

Excellent

Good

Fair

Fair

Fair

Cost effectiveness ***

Fair

Excellent

Good

Good

Fair

Good

Fair

Poor

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

* The temperature limit is based on the actual fin temperature, not necessarily the fluid temperature inside or outside the finned tube. The fin temperature is determined under

operating conditions when both fluids are flowing.

** Thermal effectiveness is based on general fin efficiency for typical operating ranges. In all applications one fin will be more thermally suited than others and that will changed

in different applications depending on the fluids, temperatures, flows and pressure drop limitations.

*** Cost effectiveness is a relative rating based on $/BTU not considering whether the particular fin might be suited for the application.

Click Here For a Description of Fin Types

 
 